Indoor air quality of academia-related workshops based on health complaints

Trakya Univ J Nat Sci. Published online 19 August 2025.
1. Air Pollution Research Department Environment and Climate Change Research Institute, National Research Centre, Giza, Egypt
No information available.
No information available
Received Date: 01.03.2025
Accepted Date: 16.07.2025
E-Pub Date: 19.08.2025
PDF
Cite
Share
Request

Abstract

Indoor Air Quality (IAQ) is a result of the interaction between micro-environmental conditions, location, and building characteristics. IAQ directly affects human health, comfort, productivity, and performance. However, very little attention has been paid to the IAQ of nonindustrial workshops.

This cross-sectional survey aimed to determine the IAQ of academia-related workshops based on the factors such as the microbial load (including bacteria, fungi, and actinomycetes), particulate matter (PM) content, presence of chemical pollutants (such as ammonia [NH3], volatile organic compounds [VOCs], and formaldehyde [HCHO]), and physical conditions (such as temperature [T°C], relative humidity [RH%], light intensity, noise, dewpoint and air speed). Moreover, the perception weights of IAQ factors affecting the indoor comfort condition were also examined.

A two-stage viable, Andersen cascade impactor, was used by suctioning air onto the selective culture media. The PM content was determined by using a preweighted membrane filter. Portable air quality monitors were used to estimate the chemical and physical factors. A questionnaire survey was employed to assess the health complaints and the participants’ perception weights on the indoor environmental parameters (such as thermal, acoustic, visual environment, and air quality).

The concentrations of mesophilic bacteria, fungi, and actinomycetes were found to be higher indoors than outdoors, with indoor/outdoor (I/O) values of 3.13, 1.56, and 1.53, respectively. The Global Index of Microbial Contamination/m3 exceeded 7,000 colony forming units/m3 in approximately 46% of the workshop areas. The I/O ratios of PM, VOCs, HCHO, and NH3 were 1.69, 1.52, 0.65, and 0.6, respectively. T°C and RH% values ranged 18–35°C and 40–56%, respectively. Noise values exceeded 70 dBA in both the indoor and outdoor environments. Light intensity was also unacceptable (≤ 300 lux) at 84.6% of the workshop areas. VOCs and dewpoint revealed significant positive and negative effects on microbial viability, differing with regard to the microbial type. Fatigue (45.5%), allergies (38.6%), and headache (35.2%) were the common complaints of the occupants. All of the tested IAQ parameters influenced the workplace environment, with noise ranking as the main factor (40.9%).

Microbial air quality is differently associated with the indoor environmental factors. The IAQ in the workshops was poor and potentially affected the occupant’s well-being. The perception of comfort varied among the occupants under the same IAQ factors. Thus, corrective actions based on comparative analysis should be implemented to promote the indoor quality of even nonindustrial and academia-related workplaces.

Keywords:
indoor air quality, nonindustrial workshops, deposited dust, particulate morphology, microorganisms, VOCs, noise, lighting, health complaint, satisfaction

Introduction

Indoor Air Quality (IAQ) is influenced by multiple interrelated factors, including building activities and materials, ventilation efficiency, emission sources, and both geographical and microclimatic conditions (Apte & Salvi, 2016; Tran et al., 2020; Chawla et al., 2023). Air pollutants, thermal comfort, illumination level, and noise pollution are the key factors that significantly impact IAQ (Tang et al., 2020; Roumi et al., 2022; Wu et al., 2023). Indoor air pollution levels are often reported to be 2–5 times higher than outdoor (United States Environmental Protection Agency [U.S. EPA], 2025a), with indoor environments emitting wide array of hazardous pollutants such as volatile organic compounds (VOCs), particulate matter (PM), and microorganisms (Kumar & Imam, 2013).

Among these pollutants, microorganisms are pervasive in indoor environments, and present substantial public health risks (DiCarlo et al., 2016; U.S. EPA, 2025b). Numerous studies have evaluated microbial air quality across both industrial (Gilbert & Duchaine, 2009; Mackiewicz et al., 2015; Thorne, 2019; Quintana et al., 2020; Quintanilla-Martinez et al., 2022; Tyagi & Srivastava, 2023) and public (Shiferaw et al., 2016; Osman et al., 2017; Abdel Hameed et al., 2018; Pyrri et al., 2020; Nath et al., 2023) settings. The diversity and concentration of microbial populations in indoor air are shaped by geographical location, weather conditions, and human activities (Rai et al., 2021). Inhalation exposure to airborne microbes can trigger respiratory infections, allergic reactions, hospital-acquired (nosocomial) diseases, and symptoms associated with sick building syndrome (SBS) (Dyląg, 2017). Furthermore, microbial contamination contributes to the biodeterioration of structural materials (Kadaifciler, 2017; Lippai et al., 2024).

PM, one of the most critical indoor pollutants, is composed of both primary particles (emitted directly from anthropogenic or natural sources) and secondary particles (formed through complex chemical reactions in the atmosphere) (Juda-Rezler et al., 2020). Indoor PM concentrations are influenced by external air quality, building envelope characteristics, ventilation rates, material composition, and human activities (Cheng, 2017; Melymuk et al., 2020). Elevated PM levels have been documented in specific workplaces, including metal and wood working facilities (Abdel Hameed et al., 2000; Insley et al., 2019, Buljat et al., 2024). The shape, size, and chemical composition of PM vary significantly, which determines its toxicity and surface-soiling potential (DiBernardino et al., 2021; Park et al., 2018). Therefore, both the mass concentration and chemical composition of PM should be analyzed to understand its full impact on human health.

VOCs are another critical group of indoor air contaminants, consistently found in higher concentrations indoors compared to outdoor (Nurmatov et al., 2015; Spinazzè et al., 2020). VOCs, including formaldehyde (HCHO), are released from a range of sources such as building materials, insulation foams, cleaning agents, furnishings, and human activities (Mangotra & Singh, 2024). Building materials alone can contribute up to 40% of total indoor VOCs emissions, depending on the building’s age, type, and prevailing temperature and humidity conditions (Missia et al., 2010; Zhu et al., 2024). Notably, newly constructed or recently renovated buildings exhibit significantly higher VOC levels than older structures (Holøs et al., 2018). In Chinese residential, educational, and office buildings, median HCHO concentrations ranged between 94–163 µg/m³, with 46–91% of sampled buildings, exceeding the standard threshold of 100 µg/m³ (Fang et al., 2022). Formaldehyde is classified as a Group 1 human carcinogen by the International Agency for Research on Cancer IARC, 2006).

Ammonia (NH3) is a dominant basic gas present in both indoor and outdoor environments (Li et al., 2020). Emissions originate from various sources, including livestock, decomposition of organic matter, industrial and vehicular emissions, combustion activities, building materials, paints, and even human metabolism and exhaled breath (Li et al., 2022; Lefferts & Castell, 2022). NH3 also plays a critical role in atmospheric chemistry, particularly in the formation of secondary PM (Wyer et al., 2022). Studies from Chinese college dormitories reported mean NH3 concentrations of 0.59 mg/m³, exceeding the national standard threshold (GB/T 18883–2002). Chronic exposure to NH3 has been linked to neurophysiological disturbances, mucous membrane irritation, and headache (California Office of Environmental Health Hazard Assessment, 1999; Pacharra et al., 2016; Sun et al., 2024).

Physical parameters, including thermal conditions, directly affect both IAQ and occupant well-being (Asadi et al., 2017). Thermal discomfort, particularly temperatures > 26°C, has been shown to negatively impact productivity (Lan et al., 2011), whereas uncontrolled fluctuations in temperature and humidity can damage building materials (Camuffo, 2019). High temperatures, low air exchange, elevated humidity, excessive light intensity, and poor air quality are commonly associated with SBS symptoms (Akova et al., 2022).

A prior assessment of academia workshop environments categorized their indoor environmental quality (IEQ) as Class D (IIEQ score of 10–32.5), indicating a high-risk classification according to the IEQ Index model (Abdel Hameed et al., 2023). Walkthrough inspections of these workshops revealed several concerns, including high humidity levels, visible dust and dirt accumulation, inadequate ventilation, fungal growth, and musty odors. Occupants also reported health-related complaints potentially linked to these environmental deficiencies.

Given these observations, the present study aims to investigate IAQ-related factors within academic workshop settings; examine the influence of micro-environmental parameters on airborne microbial composition; identify the prevalence and extent of indoor fungal contamination; and determine the perception weightage of various IAQ factors to pinpoint the primary contributors to occupant satisfaction. The findings are intended to draw attention to potential IAQ hazards in nonindustrial academic and public workshop settings, and support the development of threshold guidance values tailored for such environments.

Materials and Methods

IAQ Factors and Sampling Workshops

A cross-sectional survey of IAQ (including microbial, PM, chemical, and physical) factors was conducted in 13 workshops related to academia building. The workshops are namely “wood, alumina, glass, painting, plumbing, welding, car garage & maintenance, scientific equipment maintenance, cooling, oil extraction, marble and granite test, water pump station, and electricity station.” These workshops cannot be classified as the same as industrial workshops despite performing technical/or professional tasks related to public building activities. The workshops are located in different buildings and differ in their total area (range: 40‒187 m2), height above the ground level (‒3 m to + 6 m), number of occupants (range: 3‒22 persons/location), and ventilation mode. Poor ventilation rate, dampness, musty odor, and crowding are the common characteristics of the workshops. Natural ventilation (openings) is the main ventilation type; however, mechanical ventilation (fans/no air conditioner) is operated in some workshops. The academic building is located in the Dokki district, Giza governorate. This district is an urban area characterized by heavy anthropogenic activities, high traffic, commercial activities, hospitals, offices, and numerous educational facilities, with rare and permanent vegetation cover. The description of the sampling sites and timetable schedule for the IAQ measurements has been presented in Table 1.

Sampling Campaign

A total of 28 samples (a minimum of 2 event/workshop) and 6 samples (at least one sample/month) were collected from inside and outside the workshops, respectively. The sampler/monitor was placed at approximately 1.5‒2 m height on a flat surface, approximately 1‒2 m away from the openings and disturbance of direct obstacles. The outdoor sampling was conducted approximately 3‒4 m outside of the main building, away from any distinct emission sources. The indoor and outdoor samples were almost collected in parallel.

The measurements of the chemical and physical parameters were performed at the beginning and the end of each sampling event (approximately 2 readings/event), except for the PM, with one PM sample collected at every sampling event. The air samples were collected during the normal working days, which lasted approximately 4‒5 h, during 10:00 and 15:00 hours, which is the period of full capacity of the work activity. The sampling was conducted on Mondays through Thursdays of the last weeks of each month, during the period between May and December 2022.

Sampling of the Airborne Microorganisms

A two-stage viable particle sampler (TE-10-160, Tisch Environmental Cleves, OH, USA) was used to collect airborne microorganisms (National Institute for Occupational Safety and Health, 1998). This device separates particles into fine (≤ 2.5 µm) and coarse (≥ 7 µm) size ranges and operates at the recommended flow rate of 28.3 L/min for 5 min; it was run in duplicate. Trypticase soya agar supplemented with 0.25% cycloheximide, malt extract agar supplemented with 0.01% chloramphenicol, and starch casein agar media were used to culture bacteria, fungi, and actinomycetes, respectively. The culture plates of fungi and actinomycetes were incubated at 28°C ± 2°C for 5 and 7–14 days, respectively, whereas those of environmental and mesophilic (human-related) bacteria were incubated at 30°C ± 2°C for 48 h and at 37°C for 48–72 h, respectively. Positive hole correction was applied to the raw colony forming unit (CFU) recorded on each plate and by using the CFU with sampling time and flow rate; the concentration was calculated and expressed as CFU/m3 of air (Andersen, 1958).

Fungal isolates were identified through direct observation of micro- and macro-morphological features by reverse and surface coloration of colonies on Sabouraud’s dextrose agar, Czapek dox agar, potato dextrose agar (Difco, Detroit, MI) and malt extract agar media (Hi-media laboratories, Mumbai, India) with the use of keys for taxonomic literature (Ellis, 1971; Raper & Fennell, 1977; Barnett & Hunter, 1999; Pitt & Hocking, 2009).

Suspended and Deposited Particulates

Suspended PM was collected on a preweighed cellulose nitrate membrane filter (25 mm-diameter, 0.45 µm-pore size) using an open face filter holder and a vacuum pump calibrated to draw 15 L/min for 4–5 h. The PM mass concentration was calculated and expressed as microgram per cubic meter of air (µg/m3). The shape (morphology) of the PM collected from some workshops was analyzed with the high-resolution scanning electron microscope (SEM; Quanta FEG 250, FEL Company, Netherlands, Electron Unit of Microscopy, NRC). The chemical species of the PM sample collected from the auto-mechanic (car maintenance) workshop were only examined by using an energy-dispersive X-ray analyzer (EDAX) attached to the electron microscope.

The deposited (settled) dust was determined using a passive collector (170-mm height, 80-mm diameter) by positioning the collector approximately 2–3 m above the floor surface in the center of the workshop. The dust collectors were harvested after 3 months of exposure, and the deposited dust was carefully transferred to dry-sterilized preweighted beakers. The dust rate was then calculated and expressed as milligram per square meter per day (mg/m2/day).

Chemical Pollutants (i.e., VOCs, HCHO & NH3)

A portable digital Aeroqual-Series 200 detector (Auckland, New Zealand) was used to measure the levels of VOCs and NH3. Moreover, a portable air quality monitor (Yvelines air quality monitor, Model: HTO-131, USA) was used to measure the HCHO levels. The levels of the chemical pollutants were expressed as milligram per cubic meter of air (mg/m3) for VOCs and as microgram per cubic meter of air (µg/m3) for HCHO and NH3.

Physical Factors (i.e., Noise, ToC, Relative Humidity [RH%], Light and Air Speed)

The noise levels were determined by using a sound level meter (model RO-1350, Taiwan) positioned approximately 1.5 m above the ground surface level, no closer than 3 m to any reflecting surface, and expressed as decibel-A (dBA). The light intensity was measured at nearly 4 points/location with a light meter (Light meter-TM-201, Taiwan) and expressed as lux. ToC and RH% were measured using a thermo-hygrometer (Sato-PC 5,000, China) (ASTM 2015). The air velocity (m/s) was measured using an anemometer (ABH-4225, Taiwan). The physical parameters were measured at the start time (10:00 – 11:00 AM) and at the end time (2:00 – 3:00 PM) of each sampling event.

Survey of the Complaints Related to the Indoor Environment

A questionnaire survey was administered to 88 randomly selected subjects, with no inclusion or exclusion criteria. The survey items were general questions based on the frequent occurrence of the health symptoms for 3 days per week in the past 4 weeks before the survey. These symptoms appeared daily or nearly every working day and disappeared/or got better when the employee left the workplace. The questionnaire listed the following general symptoms: shortness of breath, wheezing, cough, sneezing, stuffy nose, throat irritation, allergy, watering eyes, dry eyes, irritation of the eyes, headache, fatigue, dizziness, and nausea (Mendell et al., 2003; Azuma et al., 2022). Moreover, the weighting of four IAQ factors (i.e., temperature, light intensity, noise, and air quality [ventilation/odor]) that affected the occupants satisfaction was analyzed with reference to the questionnaire-based survey so as to determine the major IAQ factor affecting the worker’s comfort.

Statistical Analysis

Descriptive (i.e., range, mean, standard deviation (SD), and 95% confidence intervals) and nonparametric statistics were employed to analyze the obtained data. Spearman’s rank-correlation test was performed to determine the relationships between the chemical and physical factors with the microbial load. p ≤ 0.05 was considered to indicate statistical significance.

QA/QC

QA/QC was applied using duplicate samples in each sampling event for the determination of the microbial load and the presence of physical and chemical parameters. A blank membrane filter and culture media were maintained to standardize the PM and microbial pollutants, respectively. The sampling devices were verified against the calibrated reference equipment. Statistical analysis was performed to interpret the obtained data. The outdoor samples were collected on the same days for IAQ assessments.

Results and Discussion

Microbial Air Quality

Indoor microbial air quality depends on the shear force, microbial type, indoor sources, outdoor air quality, occupant’s intensity, nature of work, and the ventilation mode (Romano 2023). The summary of the indoor and outdoor microbial air quality is presented in Table 2 and Figure 1. The airborne microbial concentrations varied with regard to the workshops. The concentrations of environmental bacteria, mesophilic bacteria, fungi, and actinomycetes averaged 4,646 CFU/m3 (95% confidence interval [CI] 2,308–6,984 CFU/m3), 1,931 CFU/m3(95% CI 1,186–2,677 CFU/m3), 825 CFU/m3(95% CI 490–1,159 CFU/m3) and 532 CFU/m3(95% CI 153–862 CFU/m3), respectively. The indoor/outdoor (I/O) ratios were 0.95, 3.13, 1.56, and 1.53 for the corresponding microbial indicators, respectively. The highest concentration of mesophilic bacteria (4,531 CFU/m3) was recorded in the cooling workshop. The highest loads of fungi (2,841 CFU/m3) and actinomycetes (2,254 CFU/m3) were detected in the water pump workshop. Environmental bacteria (19,378 CFU/m3) were detected in the highest concentration in the marble and granite test workshop (Figure 1), suggesting that the dust-raising activities increased the bacterial counts relative to the fungal counts.

Airborne microorganisms are randomly transmitted between the indoor and outdoor environments. Indoor microorganisms originate from indoor sources and natural/or anthropogenic surrounding activities. The I/O ratios of microbial air parameters indicated that the indoor environment was the main contributor of mesophilic bacteria, fungi, and actinomycetes, whereas the outdoor environment was the main contributor of environmental bacteria. I/O value  > 1 indicates that biocontamination originates from the indoor environment (Roshan et al., 2019; Jabeen et al., 2023). Overcrowding, poor ventilation, and adequate moisture facilitate the emission of bacteria and fungi indoors (Crawford et al., 2015). Actinomycetes are not normal indoor microbial flora, and their presence has been associated with abnormal situations such as presence of dampness and mold (Nevalainen et al., 1991). Actinomycetes are associated with the complaints of odor in buildings (Nevalainen et al., 1990). The low counts of actinomycetes may be attributed to their complex natural aerosolization mechanism, considering that they have small spore sizes approximately ≤ 1 µm, which requires high air current to release them into the air (Reponen et al. 1998).

Natural ventilation, through openings, is the main ventilation mode in most workshops. The studied workshops had inadequate and bad ventilation (air velocity ≤ 0.15 m/s), which directly affected microbial concentrations and types. I/O ratio, a relative standard, was applied to establish the presence or absence of indoor biologically derived sources and the outdoor infiltration factor. Natural ventilation increases the fungal counts and mechanical ventilation reduces their counts (MacIntosh et al., 2006), and infiltration brings exogenous microbes to the indoor environment (Zhong et al., 2016). Mechanical ventilation (rarely operated at these workshops) has higher air exchange rates compared to natural ventilation, which consequently reduces the indoor microbial content (Langer & Bekö, 2013).

Indices of Biocontamination

An assessment of the contamination levels was performed using three evaluation indices for microbiological pollution, namely “Global Index of Microbial Contamination per cubic meter of air (GIMC/m3), amplification index (AI), and the index of microbial contamination (IMC), (Dacarro et al., 2005). GIMC/m3 was calculated as the sum of the total counts of microbial parameters in each workshop. IMC was determined by calculating the ratio of the CFU/m3, as measured for mesophilic and environmental bacteria at the same sampling site. AI is calculated as the ratio between the GICM/m3 values measured indoors and outdoors, and it is an indicator of microbial accumulation indoors (Grisoli et al., 2019).

The summary of the biocontamination indices in the workshops is depicted in Table 3 and Figure 2. The GIMC/m3 index values ranged between 103 CFU/m3 and 104 CFU/m3 and exceeded 7,000 CFU/m3 at nearly 46% of the total workshops. The greatest GIMC/m3 was detected in the marble and granite test workshop (22,110 CFU/m3) and the lowest in the plumbing workshop (3,373 CFU/m3) (Figure 2a). The values of the AI and IMC indices were ≥ 1 at 61.5% and 15% of the total workshops, respectively. GIMC/m3, IMC, and AI achieved the highest values in the marble and granite test, water station, and cooling workshops, respectively (Figure 2a and b). The GMIC/m3 values profile was in the following sequence: marble and granite test > water pump > cooling > electricity > wood > painting > car maintenance > alumital > repair of scientific equipment > glass > welding > oil extraction> plumbing. The workshops had higher microbial air loads (GIMC/m3≥ 7,000 CFU/m3) when compared to other public buildings, such as hospitals, libraries, schools, and child daycares in Egypt (Abdel Hameed et al., 2018).

Fungal Diversity

The identification of airborne fungal spores is a critical issue to determine their sources, health problems, and proactive steps so as to reduce the exposure. A total of 25 fungal taxa were identified at all workshops, including Absidia, Acremonium, Alternaria, Aspergillus flavus (A. flavus), Aspergillus niger, Aspergillus ochraceus, Aspergillus terreus, Aspergillus versicolor (A. versicolor), Aspergillus fumigatus (A. fumigatus), other Aspergillus, Aureobasidium, Cladosporium, Curvularia, Drechslera, Emericella, Epicoccum, Fusarium, Monilia, Nigrospora, Penicillium, Rhizopus, sterile hyphae, Trichoderma, Trichothecium, and yeast.

Aspergillus (57.9%), Penicillium (9.34%), Cladosporium (4.84%), and Alternaria (3.42%) were the dominant fungal taxa. Fungal diversity was the highest at the wood workshop (13/ 25,~52%) and lowest at the plumbing workshop (6 /25, ~24%). Aspergillus constituted the largest counts, with 36–2,699 CFU/m3, at almost all the workshops. The highest counts of Aspergillus, Alternaria, Cladosporium, and Penicillium were detected in the water pump station, painting, granite and marble test, and oil extraction workshops, respectively (Figure 3). The secondary (Alternaria, Cladosporium, A. flavus, A. versicolor, Penicillium, and Emericella) and tertiary (A. fumigatus, Nigrospora, Aureobasidium, Fusarium, Trichoderma, Monilia, yeast, and sterile hyphae) fungal colonizers grew well at moderate and high water activities, respectively.

Generally, the characteristics of the surrounding environment and buildings, human activity, ventilation rate, and microclimatic conditions affect fungal counts and diversity (Hoekstra et al., 1994; Loukou et al., 2024). The dominance of primary fungal colonizers can be attributed to the fact that they are easily liberated into the air when disturbed, can adapt to atmospheric transport, and grow well in diverse habitats with minimal nutrients. Globally, Aspergillus and Penicillium species are dominant in different climatic conditions (Mousavi et al., 2016), colonize damp materials (Horner, 2006), and prefer air humidity (Wilkie et al., 2023). The phyloplane taxa, Alternaria, Cladosporium, Epicoccum, and Drechslera (naturally grow on leaves and other plant surfaces) dominate the outdoor environment (Levetin & Dorsey, 2006). Penicillium, a soil fungus, predominates in most regions and is replaced by Aspergillus in humid environments (Lacey et al., 1991). The tertiary fungal colonizers grow on most building materials in the presence of adequate moisture, with at least 0.65 water activity required for growth (Lacey & Dutkiewicz, 1994). The presence of primary, secondary, and tertiary fungal colonies indicates the fluctuation and stratification of microclimatic conditions, which warrants intervention to control dampness and dust.

Monitoring of microbial air quality is important as a regulatory compliance as well as for biological risk assessment. Although it is difficult to establish a dose–response relationship on the basis of the existing epidemiological data, the numbers and types of microorganisms detected can offer a useful index for evaluating IAQ (Grisoli et al., 2019).

Universally, there are no acceptable/official permissible values for airborne microorganisms. The Commission of the European Communities suggests < 500 CFU/m3 and ≥ 2,000 CFU/m3as intermediate and high biocontamination, respectively, in a nonindustrial environment (Commission of the European Communities, 1993). Microbial counts > 1,000 CFU/m3 indicates biocontamination (Occupational Safety and Health Administration [OSHA], 1992). Concentrations of bacteria > 3,000 CFU/m3, fungi > 10,000 CFU/m3, and actinomycetes > 100 are suggested as strongly microbial contaminated air (Polish Standard/PN-89/Z-04111/03, 1989). Fungal count ≥ 100 CFU/m3 indicates the presence of an indoor source (Ohgke et al., 1987) and an abnormal condition when the count exceeds 500 CFU/m3 (Reynolds et al., 1990). In Sweden, the concentration of Aspergillus species should be < 50 CFU/m3 (Holmberg, 1987).

Actinomycetes count ≥ 100 CFU/m3 indicates a damp environment and high microbial pollution (Breza–Boruta & Paluszak, 2007). Miller et al. (1988) reported that toxigenic and pathogenic fungi are unacceptable in indoor air, and if one of the counts of fungal species is > 50 CFU/m3, indoor air is acceptable if the mixture of fungal species is < 150 CFU/m3 and phylloplane fungi is < 300 CFU/m3. The World Health Organization (WHO) expert group on the assessment of the health risks of biological agents in the indoor environment suggests that the l03 microorganisms/m3 is generally considered the maximum safety level (Macher et al., 1995). Microbial air counts at the academia workshops exceeded some of the previously recommended limit values.

Suspended and Deposited PM

The concentrations of the suspended and deposited dust in the workshops are presented in Table 4. The concentrations of PM were 83–536 µg/m3, with a mean of 287 µg/m3 (95% CI 172‒366 µg/m3) in the indoor environment and 169 µg/m3 (95% CI 112‒226 µg/m3) in the outdoor environment. The I/O ratio of PM was 1.69, indicating that indoor activities were the main contributor of particulates. Heavy dust contamination ≥ 400 µg/m3) was detected in the welding, glass, car maintenance, wood, marble, and granite test workshops. The greatest PM concentration (536 µg/m3) was detected in the welding workshop, as the nature and composition of the PM affected its mass concentration.

The deposited dust rate averaged 71.9 mg/m2/day (95% CI 33.5–110.3 mg/m2/day) inside the workshops. The highest and lowest deposited dust rates were detected in the wood (258 mg/m2/day) and oil extraction (1.75 mg/m2/day) workshops, respectively. Dust deposition inside the workshops widely varied, depending on the nature and capacity of the work and the infiltration factor. The calculation of the particle size is of great concern to determine the removal process and exposure risks. The particle sizes ranged between ≤ 5 and ≥ 20 µm. The deposition velocity is computed from the deposited dust rate (µg/m2/h) and volumetric concentration (µg/m3), and it is determined by the size, air turbulence, RH, thermal gradient, and eddy diffusion (Lai & Nazaroff, 2000). In this study, the lowest deposition velocity (1.3E02 cm/s) was detected in the oil extraction workshop and the highest (1.13 cm/s) in the plumbing one. Particle sizes ≤ 5 µm were detected in the oil extraction, repair of scientific equipment, and water pump workshops.

The mass concentration, composition, size, and shape of the PM vary with the dust origin and the formation process (Morawska & Salthammer, 2003; Dong et al., 2019; Zhang et al., 2022). The study of the physical properties of suspended particles helped understand their behavior and removal process. Figure 4 depicts the SEM images and EDAX analytical approach of PM. The shape of the particles varied from being fairly simple and regular to irregular/or complex ones. The shapes are varied within rounded and smooth surfaces, crystalline, and small and elongated fibers. This variation confirmed that the particles had various contributors such as fly ash, diesel soot, fossil fuel burning, and organic origin. The regular fibrous/elongated shape was detected in the wood workshop, whereas small agglomerate spherical particles were detected in the auto mechanic workshop (Figure 3). Tiwar et al. (2024) reported that quartz (rock particles) and tapered fibers dominated in the glass workshop, spherical particles (Si, Al, and Fe-rich) produced from combustion, and irregular blocky particles (Fe, Si, Ca, and Mg-rich) produced by mechanical processes.

Chemical Air Pollutants

The average values of indoor HCHO, NH3, and VOCs were 226 µg/m3 (95% CI 193‒259 µg/m3), 157 µg/m3(95% CI 90‒224 µg/m3), and 2.52 mg/m3 (95% CI 0.96‒3.74 mg/m3), respectively (Table 4). The highest values of the corresponding air chemical pollutants were measured at the electricity station (316 µg/m3), car garage and maintenance (395 µg/m3), and oil extraction (8.57 mg/m3) workplaces, respectively. The I/O ratios of HCHO, NH3, and VOCs were 0.65, 0.6, and 1.5, respectively. The indoor environment was the main contributor of VOCs. The VOCs and HCHO are generally linked and emitted from a variety of natural and human-caused sources (Hansen, 1999; Kumar et al., 2021; Dehghani et al., 2024). Surprisingly, the HCHO values were higher outdoors than indoors. HCHO is formed through the atmospheric oxidation of VOCs and the reaction among O3, alkenes, and terpenes (Liu et al., 2023) and anthropogenic sources of industrial and vehicle emissions and vegetation. HCHO values were higher in the ambient air, especially in the urban environment (Salthammer et al., 2010).

Although VOCs are the main pollutants affecting the IAQ, there are no global/local limits on them. Some countries have recommended permissible limits, such as 200 µg/m3 by Belgium, 1,000 𝜇g/m3 by South Korea (International Society of Indoor Air Quality and Climate, n.d.), and 3,000 µg/m3 by Finland (Tuomi & Vainiotalo, 2016). The value of 500 µg/m3 is recommended as a background level for VOCs (Bluyssen et al., 2005). VOCs were detected in high values, exceeding the recommended permissible limit of 3 mg/m3 at 30% of the workshop areas (such as glass, aluminum, oil extraction, and painting workshops). However, the American Conference of Government Industrial Hygienists (ACGIH, 2012), the Occupational Safety and Health Administration (OSHA, 1992),

the World Health Organization (WHO, 2000), and Danish guidelines (Nazaroff & Weschler, 2004) have recommended HCHO limit values of 370 µg/m3/8 h, 920 µg/m3/8 h, 100 µg/m3, and 100 µg/m3, respectively. HCHO values exceeding the limits have been set by the Danish guidelines and the WHO (100 µg/m3) in all workshops under investigation.

NH3 values varied at 45.6–395 µg/m3 inside the workshops, with an overall average of 157 µg/m3. The average value of NH3 was within the recommended limits of 0.2 mg/m3 (Standardization Administration of China, 2002) and 17 mg/m3 (Health and Safety Executive, 2018). NH3 values exceeded the threshold limits of 0.2 mg/m3 in 30.7% of the total studied workshops (including water pump, car maintenance, plumbing and cooling workshops). The present results are compatible with those reported for residences (0.21 mg/m3), offices (0.26 mg/m3), and school buildings (0.15 mg/m3) in China (Sun et al., 2021).

Physical Parameters

A summary of the levels of physical parameters at the workshops is presented in Table 5. Indoor and outdoor noise levels ranged at 54–87 dBA. The noise levels averaged 71 dBA (95% CI 66–76 dBA) inside and 74 dBA (95% CI 70.8–77 dBA) outside the workshops. The noise level was ≥ 70 dB in 53% of the total workshops. The noise level exceeded the minimum comfort level in the public buildings (60 dBA) in almost all the workshops, except at the oil extraction workshop (54 dBA). The highest noise level (87 dBA) was recorded at the wood workshop, exceeding the Egyptian permissible limit level of 85 dBA for the industrial sector (Egyptian Environmental Affairs Agency, 1994). The light intensity levels varied at 41‒317 lux, with an average level of 176 lux (95% CI 132–222 lux). Light intensity was detected at very low levels at the welding and plumbing workshops (41‒54 lux). The light intensity ranges (41‒317 lux) were below the acceptable minimum level of 300 lux (NP 061, 2002) at 84.6% of the total workshops.

The temperature, RH, and dew point measurements averaged 28.4°C (95% CI 25.1°C‒31.7°C), 48.8% (95% CI 46–53.7%), and 17.2 oC (95%CI 14.3°C‒20.1°C), respectively (Table 5). The highest reading of ToC (35°C) was determined at the glass workshop. The highest readings of RH% (58%) and dew point (21.4°C) were detected at the car maintenance workshop. The readings of temperature ≥ 30°C and RH ≥ 50% were, respectively, measured at 69.2% and 46.2% of the total workshops. The mean value of the RH was intermediate (48.8%), and temperature (28.4ºC) did not comply with the comfortable condition. The OSHA provides guidance for air temperature and RH ranges within 20°C–24.4°C and 20–60%, respectively (OSHA, n.d.). The dew point values exceeded the upper limit of 16.8°C (ASHRAE Standard 55, 2010) at 61.5% of the total workshops. The measurements of air velocity were below the recommended limit of 0.15–0.50 m/s (Sulaiman et al., 2013). Low air velocity causes air stagnation and, consequently, poor ventilation, helping accumulate pollutants.

Relationships Between Air Microorganisms and Environmental Stressors

The correlations between microbial air quality and environmental factors are shown in Table 6. A wide range of correlations were detected, depending on the microbial type and environmental factors. PM, HCHO, and VOCs showed similar correlation pattern with airborne microorganisms. They were negatively correlated with mesophilic bacteria, fungi, and actinomycetes and positively correlated with environmental bacteria. The VOCs and HCHO values adversely affected the bacterial and fungal viabilities. VOCs react with O2 to form open air factor, inactivating microorganisms by damaging enzymes and DNA (Donaldson & Ferris, 1975). It has been suggested that indoor activities and indoor conditions are the main contributors of VOCs, HCHO, PM, mesophilic bacteria, fungi, and actinomycetes. PM positively and negatively correlated with the microbial parameters, confirming that PM had diverse contributors. The environmental bacteria may be associated with the outdoor infiltrated PM. Mesophilic bacteria, fungi, and actinomycetes may be emitted directly from the indoor environment, independent of the PM contributors. Indoor PM has small sizes (≤ 20 µm) and a more toxic chemical composition, which may negatively affect microbial viability (Sillanpää et al., 2005). PM has detrimental/or supportive effects on microbial viability (Matthias-Maser, 1998), depending on its composition and tenacity. Moreover, PM acts as a carrier/or niche of nutrients for microorganisms and affects their behavior in the air environment (Alghamdi et al., 2014; Soleimani et al., 2022).

ToC and RH% differently affected microbial viability. ToC displayed a considerable influence on microbial viability relative to RH% (Table 5). The dew point significantly supported the survival of actinomycetes (r = 0.66, p ≤ 0.05), mesophilic bacteria (r = 0.67, p ≤ 0.05), and fungi (r = 0.42) (Table 5). Environmental bacteria significantly correlated with the dew point (r = -0.53, p ≤ 0.05), NH3 (r = -0.53, p ≤ 0.05), and VOCs (r = 0.53, p ≤ 0.05). Several studies have reported contradictory associations between airborne microorganisms and environmental factors. Dennis and Lee (1988) reported the best survival of aerosolized Legionella at 90% RH%, which was intermediate at 30% and poor at 60%. However, Hambletonet et al. (1983) found the best survival of Legionella at 65% and the worst at 90% and 30%. Frohlich-Nowoisky et al. (2014) concluded that high RH (70–80%) promoted airborne microbial survivability. The death rates of some gram-positive and gram-negative bacteria showed an increase at intermediate RH% (50–70%) to high (70–90%) (Won & Ross, 1969; Hatch et al., 1970). RH% ≤ 65% had a negative effect on the survival of airborne bacteria and fungi (Karbowska-Berent et al., 2011). Temperature ≥ 24°C decreased the survival of airborne bacteria (Tang, 2009), whereas higher temperatures increased their survival (Smets et al., 2016).

Insignificant correlations were detected between bacteria and temperature, RH, and dust level (Cho et al., 2019). Fungal concentrations were higher with high RH values (Rodriguez-Rajo et al., 2005; Erkara et al., 2008), although some researchers have reported the opposite (Sabariego et al., 2000). No correlations were detected between temperature and RH with the counts of airborne bacteria and fungi (Andriana et al., 2023). The RH negatively affects microbial viability due to the changes in the lipid bilayers of the cell membrane, which affect the cell surface protein configuration (Hurst et al., 2007).

Noise and light intensity did not affect the viability of airborne microorganisms. Light intensity and noise were positively correlated with mesophilic bacteria and fungi, and negatively with actinomycetes and environmental bacteria, respectively (Table 5). Human activity and its intensity probably raise the noise level and increase the load of resuspended microorganisms. Light has a lethal effect on microbial viability, as it produces air ions that accelerate the physical decay rate of microorganisms through attraction/agglomeration (Krueger et al., 1969; Krinsky, 1976). The positive ions cause the physical decay of microorganisms (through inactivation of the surface protein) and the negative ions exhibit physical and biological effects on DNA (Pepper & Greba, 2015). The agglomeration of bioparticles increases aerosol mass and enhances their deposition (Murdoch et al., 2013). Environmental factors synergistically affect the integrity/biological activity of microorganisms (Verreault et al., 2014). Therefore, understanding the effect of environmental factors on the survival of airborne microorganisms is critical to address their transmission and fate and design corrective actions.

Building-Related Complaints

Figure 5 shows the frequency of the health complaints related to IAQ among the workshop’s occupants. The prevalence of symptoms varied among occupants, with fatigue (45.5%), allergies (38.6%), and headache (35.2%) being the most common ones. Stuffy nose and nausea (9.1% each) were the lowest prevailing symptoms among the occupants. Little attention has been paid to optimal IAQ for public and nonindustrial settings. Fatigue and headache were the most prevalent symptoms among the Egyptian office workers, who were influenced by physical and psychosocial work conditions (Abdel-Hamid et al., 2013). Air quality, temperature, noise, ventilation rate, and lighting condition were found to affect occupants’ satisfaction (Felgueiras et al., 2023). Temperature ≥ 23°C led to thermal discomfort (Norbäck, 2009), and low RH% (≤ 50%) was related to upper respiratory symptoms (Wolkoff, 2008). The SBS symptoms were noted to intensify with temperature of 30°C relative to that at 22°C (Lan et al., 2011). Exposure to air pollutants (such as VOCs, HCHO, PM) has been related to SBS and irritation to the eyes and upper respiratory system (WHO, 2010; Kim et al., 2015; Chai et al., 2019). The occurrence of actinomycetes was associated with abnormal and hazardous situations such as moisture damage of the building (Rintala, 2011). Exposure to actinobacteria can cause infections, allergic reactions, and lung inflammation (Lacey & Crook ,1988; Schäffer et al., 2009). Occupants living in damp and moldy buildings report more symptoms of nausea, blocked nose, and fainting compared to those living in dry buildings (Platt et al., 1989).

Figure 6 displays the perception weights of satisfaction related to the four IAQ factors. The opinions of the occupants were ranked as noise (40.9%), lighting (25%), air quality (18.2%), and temperature (15.9%). There was a discrepancy between the perceptions of IAQ factors. The perception of comfort differs among people under the same IAQ. Perception is a combination of IAQ factors (WHO, 2001) and varies with respect to the threshold of IAQ factors and individual health conditions. Although temperature condition is the key factor affecting satisfaction globally, it had the least perception weight in this survey, attributable to the interaction of other factors (e.g., RH%, dew point, climatic condition, and wind speed) that enhance the comfort effect.

Finally, there is a knowledge gap in relation to workshops associated with complex public buildings and academia. The main limitations of this comparative analysis are as follows: 1) the workshops carry out tasks similar to industry settings, but they cannot be considered as a real industrial sector, which raises confusion about the applicable guidance limits, 2) low numbers of sampling events and the wide variations among the workshop types, 3) no seasonal changes were considered (which play an important role in the perception of comfort), and 4) there was uncertainty of health complaints data due to confusion between workplace-related complaints and the existing health status of the occupants.

Conclusion

The evaluation of IAQ in workshop environments is inherently complex, influenced by microenvironmental conditions, microbial composition, and the behavior of airborne pollutants. Most IAQ parameters assessed in this study failed to comply with recommended threshold values. Airborne microbial concentrations were consistently higher indoors compared to outdoor (background). Notably, the upper bound of the 95% CI for the GIMC/m³ exceeded 7,000 CFU/m³ in approximately 46% of the workshops. The detection of actinomycete counts at or above 100 CFU/m³ further indicated abnormal, potentially hazardous conditions. PM varied significantly in terms of concentration, chemical composition, size, and morphology, largely depending on the nature of workshop activities. The presence and accumulation of deposited dust pose both health risks and potential material damage. Morphological characterization of PM using SEM imaging proved useful for understanding particle behavior and identifying pollution sources. VOCs exceeded the recommended limit of 3 mg/m³ in 30% of the workshops, whereas the noise levels surpassed the 60 dBA comfort threshold in most settings. Indoor temperatures (95% CI = 25.1°C‒31.7°C) were above the optimal range of 20–24°C, although RH remained within acceptable limits (20–60%). Light intensity was found to be inadequate (≤ 300 lux) in nearly 80% of the workshops surveyed. Environmental parameters variably influenced microbial viability. VOC concentrations and dew point showed significant effects, whereas PM appeared to support the viability of environmental bacteria. These results suggest that poor IAQ may contribute to occupant health complaints, with noise being identified as the primary factor impacting occupant satisfaction. The findings underscore the urgent need for targeted IAQ management strategies, including moisture control, ventilation improvements, dust suppression, and optimized lighting conditions. Furthermore, this study highlights the necessity of establishing tailored IAQ guidelines for workshops associated with public buildings, where unique environmental and occupational conditions prevail.

Ethics

Ethics Committee Approval: Since the article does not contain any studies with human or animal subject, its approval to the ethics committee was not required.
Data Sharing Statement: All data are available within the study.
Author Contributions: Conceptualization: A.H.A.; Material supplying: S.E.G., Y.S., S.K.; Data acquisition: S.E.G., Y.S., S.K.; Data analysis/interpretation: S.E.G., Y.S., S.K.; Writing: A.H.A.; Critical review: A.H.A.
Conflict of Interest: The author declares no competing interests.
Funding: This work was funded by the National Research Centre (NRC), Dokki, Giza, Egypt.
Editor-in-Chief’s Note: Abdel Hameed Awad is a member of the editorial board of the Trakya University Journal of Natural Sciences. He was not involved in the editorial evaluation or decision-making process for this manuscript.

References

1
Abdel Hameed, A., Khoder, M., & Farag, S. (2000). Organic dust and gaseous contaminants at wood working shops. Journal of Environmental Monitoring, 2 (1), 73–76. https://doi.org/10.1039/A907102D
2
Abdel Hameed, A., Saeed, Y., El-Gendy, S. A., & Hassan, S. K. (2023). Chemical, physical and microbial parameters inside a research building environment. Egyptian Journal of Chemistry, 66 (13), 1489–1498. https://doi.org/10.21608/EJCHEM.2023.201245.7755
3
Abdel Hameed, A., Saeed, Y., Hassan, Y., Fawzy, Y., & Osman, M. (2018). Air microbial quality in certain public buildings, Egypt: A comparative study. Atmospheric Pollution Research, 9 (4), 617–626. https://doi.org/10.1016/j.apr.2017.12.014
4
Abdel-Hamid, M. A., Hakim, A. S., Elokda, S., & Mostafa, S. N. (2013). Prevalence and risk factors of sick building syndrome among office workers. Journal of the Egyptian Public Health Association, 88 (2), 109–114. https://doi.org/10.1097/01.EPX.0000431629.28378.c0
5
American Conference of Governmental Industrial Hygienists (ACGIH). (2012). Threshold limit values for chemical substances and physical agents and biological exposure indices. ACGIH.
6
Akova, İ., Kılıç, E., Sümer, H., & Keklikçi, T. (2022). Prevalence of sick building syndrome in hospital staff and its relationship with indoor environmental quality. International Journal of Environmental Health Research, 32 (6), 1204–1219. https://doi.org/10.1080/09603123.2020.1862067
7
Alghamdi, A. M., Shamy, M., Redal, M. A., Khoder, M., Abdel Hameed, A., & Elserougy, S. (2014). Microorganisms associated particulate matter: A preliminary study. Science of The Total Environment, 479–480 , 109–116. https://doi.org/10.1016/j.scitotenv.2014.02.006
8
Andersen, A. A. (1958). New sampler for the collection, sizing and enumeration of viable airborne particles. Journal of Bacteriology, 76 (5), 471–484. https://doi.org/10.1128/jb.76.5.471-484.1958
9
Andriana, Y., Widodo, A. D. W., & Endraswari, P. D. (2023). A correlation between the number of airborne bacteria and fungi using the settle plate method with temperature and relative humidity at the clinical microbiology laboratory of Dr. Soetomo Regional General Hospital Surabaya, Indonesia. Journal of Pure and Applied Microbiology, 17 (2), 942–950. https://doi.org/10.22207/JPAM.17.2.24
10
Apte, K., & Salvi, S. (2016). Household air pollution and its effects on health. F1000Research, 5 , F1000 Faculty Rev-2593. https://doi.org/10.12688/f1000research.7552.1
11
Asadi, I., Mahyuddin, N., & Shafigh, P. (2017). A review on indoor environmental quality (IEQ) and energy consumption in building based on occupant behavior. Facilities, 35 (11/12), 684–695. https://doi.org/10.1108/F-06-2016-0062
12
American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). (2010). Standard 55-2010: Thermal environmental conditions for human occupancy. ASHRAE.
13
ASTM International. (2015). Standard test method for measuring humidity with a psychrometer (E337–15). ASTM International.
14
Azuma, K., Kagi, N., Yanagi, U., Kim, H., & Osawa, H. (2022). A longitudinal study on the effects of hygro-thermal conditions and indoor air pollutants on building-related symptoms in office buildings. Indoor Air, 32 , e13164. https://doi.org/10.1111/ina.13164
15
Barnett, H. L., & Hunter, B. B. (1999). Illustrated genera of imperfect fungi (4th ed.). The American Phytopathological Society.
16
Bluyssen, P., de Oliveira Fernandes, E., Fanger, P. O., Groes, L., Clausen, G., Roulet, C. A., Bernhard, C. A., & Valbjørn, Ø. (2005). European audit project to optimise indoor air quality and energy consumption in office buildings. TNO Report. https://www.researchgate.net/publication/37460762
17
Breza–Boruta, B., & Paluszak, Z. (2007). Influence of water treatment plant on microbiological composition of air bioaerosols. Polish Journal of Environmental Studies, 16 (5), 663–670.
18
Buljat, A., Čargonja, M., & Mekterović, D. (2024). Source apportionment of particulate matter in a metal workshop. International Journal of Environmental Research and Public Health, 21 (6), 768. https://doi.org/10.3390/ijerph21060768
19
Camuffo, D. (2019). Microclimate for cultural heritage: Measurement, risk assessment, conservation, restoration, and maintenance of indoor and outdoor monuments (2nd ed.). Elsevier.
20
California Office of Environmental Health Hazard Assessment. (1999). Ammonia, Appendix D.2: Chronic RELs and toxicity summaries. https://oehha.ca.gov/media/downloads/crnr/appendixd2final.pdf
21
Commission of the European Communities. (1993). Report No. 12: Biological particles in indoor environments. Luxembourg.
22
Chai, G., He, H., Sha, Y., Zhai, G., & Zong, S. (2019). Effect of PM2.5 on daily outpatient visits for respiratory diseases in Lanzhou, China. Science of The Total Environment, 649 , 1563–1572. https://doi.org/10.1016/j.scitotenv.2018.08.384
23
Chawla, H., Anand, P., Garg, K., Bhagat, N., Varmani, S. G., Bansal, T., McBain, A. J., & Marwah, R. G. (2023). A comprehensive review of microbial contamination in the indoor environment: Sources, sampling, health risks, and mitigation strategies. Frontiers in Public Health, 11. https://doi.org/10.3389/fpubh.2023.1285393
24
Cheng, Y.-H. (2017). Measuring indoor particulate matter concentrations and size distributions at different time periods to identify potential sources in an office building in Taipei City. Building and Environment, 123 , 446–457. https://doi.org/10.1016/j.buildenv.2017.07.025
25
Cho, E. M., Hong, H. J., Park, S. H., Yoon, D. K., Goung, S. J. N., & Lee, C. M. (2019). Distribution and influencing factors of airborne bacteria in public facilities used by pollution-sensitive population: A meta-analysis. International Journal of Environmental Research and Public Health, 16 , 1483. https://doi.org/10.3390/ijerph16091483
26
Cox, C. S. (1998). The microbiology of air. In L. Collier, A. Balows, & M. Sussman (Eds.), Topley & Wilson’s microbiology and microbial infections (9th ed., pp. 339–350). Arnold, Oxford University Press.
27
Crawford, J. A., Rosenbaum, P. F., Anagnost, S. E., Hunt, A., & Abraham, J. L. (2015). Indicators of airborne fungal concentrations in urban homes: Understanding the conditions that affect indoor fungal exposures. Science of The Total Environment, 517 , 113–124. https://doi.org/10.1016/j.scitotenv.2015.02.060
28
Dacarro, C., Grisoli, P., Del, F. G., Villani, S., Grignani, E., & Cotta, D. (2005). Microorganisms and dust exposure in an Italian grain-mill. Journal of Applied Microbiology, 98 (1), 163–171. https://doi.org/10.1111/j.1365-2672.2004.02437.x
29
Dehghani, M. H., Bashardoust, P., Zirrahi, F., Ajami, B., Ghalhari, M. R., & others. (2024). Environmental and health effects due to volatile organic compounds. In M. H. Dehghani, R. R. Karri, T. Vera, & S. K. M. Hassan (Eds.), Health effects of indoor air pollution (pp. 191–221). Academic Press. https://doi.org/10.1016/B978-0-443-16090-5.00003-9
30
Dennis, P. J., & Lee, J. V. (1988). Differences in aerosol survival between pathogenic and non-pathogenic strains of Legionella pneumophila serogroup 1. Journal of Applied Bacteriology, 65 , 135–141. https://doi.org/10.1111/j.1365-2672.1988.tb01501.x
31
DiBernardino, A., Iannarelli, A. M., Casadio, S., Perrino, C., Barnaba, F., Tofful, L., & others. (2021). Impact of synoptic meteorological conditions on air quality in three different case studies in Rome, Italy. Atmospheric Pollution Research, 12 (4), 76–88. https://doi.org/10.1016/j.apr.2021.02.019
32
DiCarlo, E., Chisesi, R., Barresi, G., Barbaro, S., Lombardo, G., Rotolo, V., Sebastianelli, M., Travagliato, G., & Palla, F. (2016). Fungi and bacteria in indoor cultural heritage environments: Microbial-related risks for artworks and human health. Environment and Ecology Research, 4 (5), 257–264. https://doi.org/10.13189/eer.2016.040504
33
Donaldson, A. I., & Ferris, N. P. (1975). Survival of foot-and-mouth disease virus in open air conditions. The Journal of Hygiene, 74 (3), 409–416. https://doi.org/10.1017/s002217240004691x
34
Dong, T., Zhang, Y., Jia, S., Shang, H., Fang, W., Chen, D., & Fang, M. (2019). Human indoor exposome of chemicals in dust and risk prioritization using EPA’s ToxCast database. Environmental Science & Technology, 53 (12), 7045–7054. https://doi.org/10.1021/acs.est.9b00280
35
Dylag, M. (2017). Fungi present in home and their impact on human health-A short review. Insights in Biology and Medicine, 1 (1), 016 -025. https://doi.org/10.29328/journal.hjbm.1001003
36
Egyptian Environmental Affairs Agency (EEAA). (1994). Law No. 4/1994 Promulgating the Environment Law and its Executive Regulation. Presidential Decree (4), 130. http://extwprlegs1.fao.org/docs/pdf/egy4984E.pdf
37
Ellis, M. B. (1971). Dematiaceous hyphomycetes (p. 608). The Western Press Ltd.
38
Erkara, I. P., Asan, A., Yilmaz, V., Pehlivan, S., & Okten, S. S. (2008). Airborne Alternaria and Cladosporium species and relationship with meteorological conditions in Eskisehir City, Turkey. Environmental Monitoring and Assessment, 144 , 31–41. https://doi.org/10.1007/s10661-007-9939-0
39
Fang, L., Liu, N., Liu, W., Mo, J., Zhao, Z., Kan, H., Deng, F., Huang, C., Zhao, B., & others. (2022). Indoor formaldehyde levels in residences, schools, and offices in China in the past 30 years: A systematic review. Indoor Air, 32 (10), e13141. https://doi.org/10.1111/ina.13141
40
Felgueiras, F., Mourão, Z., Moreira, A., & Fonseca-Gabriel, M. (2023). Indoor environmental quality in offices and risk of health and productivity complaints at work: A literature review. Journal of Hazardous Materials Advances, 10 , 100314. https://doi.org/10.1016/j.hazadv.2023.100314
41
Frohlich-Nowoisky, J., Nespoli, C. R., Pickersgill, D. A., Galand, P. E., Muller-Germann, I., Nunes, T., Cardoso, J. G., Almeida, S. M., Pio, C., & others. (2014). Diversity and seasonal dynamics of airborne archaea. Biogeosciences, 11 , 6067–6079. https://doi.org/10.5194/bg-11-6067-2014
42
GB/T 18883. (2002). Indoor air quality standard. National Standard of China. https://www.chinesestandard.net/PDF.aspx/GBT18883-2002
43
Gilbert, Y., & Duchaine, C. (2009). Bioaerosols in industrial environments: A review. Canadian Journal of Civil Engineering, 36 (12), 1873–1886. https://doi.org/10.1139/L09-117
44
Grisoli, P., Albertoni, M., & Rodolfi, M. (2019). Application of airborne microorganism indexes in offices, gyms, and libraries. Applied Sciences, 9 (6), 1101. https://doi.org/10.3390/app9061101
45
Hambleton, P., Broster, M., Dennis, P., Henstridge, R., Fitzgeorge, R., & Conlan, J. (1983). Survival of virulent Legionella pneumophila in aerosols. Journal of Hygiene, 90 (3), 451–460. https://doi.org/10.1017/s0022172400029090
46
Hansen, D. L. (1999). Indoor air quality issues. Taylor and Francis.
47
Hatch, M. T., Wright, D. N., & Bailey, G. D. (1970). Response of airborne Mycoplasma pneumoniae to abrupt changes in relative humidity. Applied Microbiology, 19 (2), 232–238. https://doi.org/10.1128/am.19.2.232-238.1970
48
Hoekstra, E. S., Samson, R. A., & Verhoeff, A. P. (1994). Fungal propagules in house dust: A qualitative analysis. In Health implications of fungi in indoor environments (pp. 169–177). Elsevier Science B.V.
49
Holmberg, K. (1987). Indoor mould exposure and health effects. In B. Seifen, H. Esdorn, M. Fischer, H. Ruden, & J. Wegner (Eds.), Proceedings of Indoor Air ‘87 (Vol. 1, pp. 637–642). Institute of Water, Soil and Air Hygiene.
50
Holøs, S. B., Yang, A., Lind, M., Thunshelle, K., Schild, P., & Mysen, M. (2018). VOC emission rates in newly built and renovated buildings, and the influence of ventilation – A review and meta-analysis. International Journal of Ventilation, 18 (3), 153–166. https://doi.org/10.1080/14733315.2018.1435026
51
Horner, W. E. (2006). Managing building-related Aspergillus exposure. Medical Mycology, 44 (1), S33–S38. https://doi.org/10.1080/13693780600925194
52
Health and Safety Executive (HSE). (2018). Workplace exposure limits: EH40/2005 (3rd ed.). HSE Books.
53
Hurst, C. I., Knudsen, G. T., McInerney, M. J., Stetzenbach, L. D., & Walter, M. V. (2007). Manual of environmental microbiology (pp. 661–663). ASM Press.
54
Insley, A. L., Maskrey, J. R., Hallett, L. A., Reid, R. C., Hynds, E. S., Winter, C., & Panko, J. M. (2019). Occupational survey of airborne metal exposures to welders, metalworkers, and bystanders in small fabrication shops. Journal of
55
Occupational and Environmental Hygiene, 16 (6), 410–421. https://doi.org/10.1080/15459624.2019.1603389
56
International Agency for Research on Cancer (IARC). (2006). Formaldehyde, 2-butoxyethanol and 1-tert-butoxypropan-2-ol (IARC monographs on the evaluation of carcinogenic risks to humans, Vol. 88).
57
International Society of Indoor Air Quality and Climate, Scientific and Technical Committee 34. (2025). Indoor environmental quality guidelines database. https://ieqguidelines.org/
58
Jabeen, R., Kizhisseri, M. I., Mayanaik, S. N., & Mohamed, M. M. (2023). Bioaerosol assessment in indoor and outdoor environments: A case study from India. Scientific Reports, 13 , Article 18066. https://doi.org/10.1038/s41598-023-44315-z
59
Juda-Rezler, K., Reizer, M., Maciejewska, K., Błaszczak, B., & Klejnowski, K. (2020). Characterization of atmospheric PM2.5 sources at a Central European urban background site. Science of The Total Environment, 713 , 136729. https://doi.org/10.1016/j.scitotenv.2020.136729
60
Kadaifciler, D. G. (2017). Bioaerosols assessment in the library of Istanbul University and fungal flora associated with paper deterioration. Aerobiologia, 33 (1), 151–166. https://doi.org/10.1007/s10453-016-9457-z
61
Kang, S., Ou, D., & Mak, C. M. (2017). The impact of indoor environmental quality on work productivity in university open-plan research offices. Building and Environment, 124 , 78–89. https://doi.org/10.1016/j.buildenv.2017.07.003
62
Karbowska-Berent, J., Górny, R. L., Strzelczyk, A. B., & Wlazło, A. (2011). Airborne and dust borne microorganisms in selected Polish libraries and archives. Building and Environment, 46 (10), 1872–1879. https://doi.org/10.1016/j.buildenv.2011.03.007
63
Kim, K.-H., Kabir, E., & Kabir, S. (2015). A review on the human health impact of airborne particulate matter. Environment International, 74 , 136–143. https://doi.org/10.1016/j.envint.2014.10.005
64
Krinsky, N. I. (1976). Cellular damage initiated by visible light. In The survival of vegetative microbes: Symposium of the Society for General Microbiology (Vol. 26, pp. 209–239). [Google Scholar]
65
Krueger, A. P., Kotaka, S., & Andriese, P. C. (1969). Atmospheric ions and aerosols. In R. I. Dimmick & A. B. Akers (Eds.), An introduction to experimental aerobiology (pp. 100–112). Wiley Interscience.
66
Kumar, P., & Imam, B. (2013). Footprints of air pollution and changing environment on the sustainability of built infrastructure. Science of The Total Environment, 444 , 85–101. https://doi.org/10.1016/j.scitotenv.2012.11.056
67
Kumar, P., Kausar, A. M., Singh, A. B., & Singh, R. (2021). Biological contaminants in the indoor air environment and their impacts on human health. Air Quality, Atmosphere & Health, 14 (11), 1723–1736. https://doi.org/10.1007/s11869-021-00978-z
68
Lacey, J., & Crook, B. (1988). Fungal and actinomycete spores as pollutants of the workplace and occupational allergens. Annals of Occupational Hygiene, 32 , 515–533. https://doi.org/10.1093/annhyg/32.4.515
69
Lacey, J., & Dutkiewicz, J. (1994). Bioaerosols and occupational lung disease. Journal of Aerosol Science, 25 (8), 1371–1404. https://doi.org/10.1016/0021-8502(94)90215-1
70
Lacey, J., Ramakrishna, N., Hamer, A., Magan, N., & Marfleet, I. (1991). Grain fungi. In D. K. Arora, K. G. Mukerji, & E. H. Marth (Eds.), Handbook of Applied Mycology (Vol. 3, pp. 121–177). Marcel Dekker.
71
Lai, A. C. K., & Nazaroff, W. W. (2000). Modeling indoor particle deposition from turbulent flow onto smooth surfaces. Journal of Aerosol Science, 31 (4), 463–476. https://doi.org/10.1016/S0021-8502(99)00536-4
72
Lan, L., Wargocki, D. P., Wyon, D. P., & Lian, Z. (2011). Effects of thermal discomfort in an office on perceived air quality, SBS symptoms, physiological responses, and human performance. Indoor Air, 21 (5), 376–390. https://doi.org/10.1111/j.1600-0668.2011.00714.x
73
Langer, S., & Bekö, G. (2013). Indoor air quality in the Swedish housing stock and its dependence on building characteristics. Building and Environment, 69 , 44–54. https://doi.org/10.1016/j.buildenv.2013.07.013
74
Lefferts, M. J., & Castell, M. R. (2022). Ammonia breath analysis. Sensors and Diagnostics, 1 , 955–967. https://doi.org/10.1039/D2SD00089J
75
Levetin, E., & Dorsey, K. (2006). Contribution of leaf surface fungi to the air spora. Aerobiologia, 22 , 3–12. https://doi.org/10.1007/s10453-005-9012-9
76
Li, M., Weschler, C. J., Bekö, G., Wargocki, P., Lucic, G., & Williams, J. (2020). Human ammonia emission rates under various indoor environmental conditions. Environmental Science & Technology, 54 (9), 5419–5428. https://doi.org/10.1021/acs.est.0c00094
77
Li, J., Xu, W., You, B., & Sun, Y. (2022). Dynamic variations of ammonia in various life spaces and seasons and the influences of human activities. Building and Environment, 212 , 108820. https://doi.org/10.1016/j.buildenv.2022.108820
78
Lighthart, B., & Shaffer, B. T. (1997). Increased airborne bacterial survival as a function of particle content and size. Aerosol Science and Technology, 27 , 439–446. https://doi.org/10.1080/02786829708965483
79
Lippai, A., Leelőssy, Á., & Magyar, D. (2024). Indoor and outdoor air microbial contamination during different reconstruction methods of historic buildings. Pathogens, 13 (12), 1048. https://doi.org/10.3390/pathogens13121048
80
Liu, T., Lin, Y., Chen, J., Chen, G., Yang, C., Xu, L., Li, M., Fan, X., Zhang, F., & Hong, Y. (2023). Pollution mechanisms and photochemical effects of atmospheric HCHO in a coastal city of southeast China. Science of The Total Environment, 859 (Part 1), 160210. https://doi.org/10.1016/j.scitotenv.2022.160210
81
Loukou, E., Jensen, N. F., Rohde, L., & Andersen, B. (2024). Damp buildings: Associated fungi and how to find them. Journal of Fungi, 10 (2), 108. https://doi.org/10.3390/jof10020108
82
Macher, J. M., et al. (1995). Sampling airborne microorganisms and aeroallergens. In B. S. Cohen & S. V. Hering (Eds.), Air sampling instruments for evaluation of atmospheric contaminants (8th ed., pp. 589–617). ACGIH.
83
MacIntosh, D. L., Brightman, H. S., Baker, B. J., Myatt, T. A., Stewart, J. H., & McCarthy, J. F. (2006). Airborne fungal spores in a cross-sectional study of office buildings. Journal of Occupational and Environmental Hygiene, 3 (7), 379–389. https://doi.org/10.1080/10543400600760438
84
Mackiewicz, B., Skórska, C., & Dutkiewicz, J. (2015). Relationship between concentrations of microbiological agents in the air of agricultural settings and occurrence of work-related symptoms in exposed persons. Annals of Agricultural and Environmental Medicine, 22 (3), 473–477. https://doi.org/10.5604/12321966.1167717
85
Mangotra, A., & Singh, S. K. (2024). Volatile organic compounds: A threat to the environment and health hazards to living organisms – A review. Journal of Biotechnology, 382 , 51–69. https://doi.org/10.1016/j.jbiotec.2023.12.013
86
Matthias-Maser, S. (1998). Primary biological aerosol particles: Their significance, sources, sampling methods, and size distribution in the atmosphere. In R. M. Harrison & R. E. Van Grieken (Eds.), Environmental particles (pp. 349–369). Wiley.
87
Melymuk, L., Demirtepe, H., & Rozárka Jílková, S. (2020). Indoor dust and associated chemical exposures. Current Opinion in Environmental Science & Health, 15 , 1–6. https://doi.org/10.1016/j.coesh.2020.01.005
88
Mendell, M. J., Naco, G. M., Wilcox, T. G., & Sieber, W. K. (2003). Environmental risk factors and work-related lower respiratory symptoms in 80 office buildings: An exploratory analysis of NIOSH data. American Journal of Industrial Medicine, 43 (6), 630–641. https://doi.org/10.1002/ajim.10211
89
Miller, J. D., Laflamme, A. M., Sobol, Y., Lafontaine, P., & Greenhalgh, R. (1988). Fungi and fungal products in some Canadian houses. International Biodeterioration, 24 (2), 103–120. https://doi.org/10.1016/0265-3036(88)90053-X
90
Missia, D., Demetriou, E., Michael, N., Tolis, E. I., & Bartzis, J. G. (2010). Indoor exposure from building materials: A field study. Atmospheric Environment, 44 (35), 4388–4395. https://doi.org/10.1016/j.atmosenv.2010.07.049
91
Morawska, L., & Salthammer, T. (2003). Fundamentals of indoor particles and settled dust. In L. Morawska & T. Salthammer (Eds.), Indoor environment (pp. 1–36). Wiley-VCH.
92
Mousavi, B., Hedayati, M. T., Hedayati, N., Ilkit, M., & Syedmousavi, S. (2016). Aspergillus species in indoor environments and their possible occupational and public health hazards. Current Medical Mycology, 2 (1), 36–42. https://doi.org/10.18869/acadpub.cmm.2.1.36
93
Murdoch, L. E., McKenzie, K., Maclean, M., MacGregor, S. J., & Anderson, J. G. (2013). Lethal effects of high-intensity violet 405-nm light on Saccharomyces cerevisiae , Candida albicans , and on dormant and germinating spores of Aspergillus niger. Fungal Biology, 117 (7), 519–527. https://doi.org/10.1016/j.funbio.2013.05.004
94
Nath, A., Baruah, N., Nonglait, M. L., et al. (2023). Biological contaminants in indoor environments of educational institutions. Aerobiologia, 39 , 1–20. https://doi.org/10.1007/s10453-022-09771-6
95
Nazaroff, W. W., & Weschler, C. J. (2004). Cleaning products and air fresheners; Exposure to primary and secondary air pollutants. Atmospheric Environment, 38 (18), 2841–2865. https://doi.org/10.1016/j.atmosenv.2004.02.040
96
Nevalainen, A., Pasanen, A.-L., Niininen, M., Reponen, T., Jantunen, M. J., & Kalliokoski, P. (1991). The indoor air quality in Finnish homes with mold problems. Environment International, 17 , 299–302. https://doi.org/10.1016/0160-4120(91)90015-I
97
Nevalainen, A., Heinonen-Tanski, H., & Savolainen, R. (1990). Indoor and outdoor occurrence of Pseudomonas bacteria. In Indoor Air ’90: Proceedings of the Fifth International Conference on Indoor Air Quality and Climate (Vol. 2, pp. 51–53). Canada Mortgage and Housing Corporation.
98
National Institute for Occupational Safety and Health. (1998). NIOSH method 0800: NIOSH manual of analytical methods.
99
Norbäck, D. (2009). An update on sick building syndrome. Current Opinion in Allergy and Clinical Immunology, 9 (1), 55–59. https://doi.org/10.1097/ACI.0b013e32831f8f08
100
NP 061. (2002). Normativ pentru proiectarea şi executarea sistemelor de iluminat artificial din clădiri.
101
Nurmatov, U. B., Tagiyeva, N., Semple, S., Devereux, G., & Sheikh, A. (2015). Volatile organic compounds and risk of asthma and allergy: A systematic review. European Respiratory Review, 24 (135), 92–101. https://doi.org/10.1183/09059180.00000714
102
Ohgke, H., Geers, A., & Beckert, J. (1987). Fungal load of indoor air in historical and newly constructed buildings used by public services. In Proceedings of the 4th International Conference on Indoor Air Quality and Climate (Vol. 1, pp. 681–684).
103
Occupational Safety and Health Administration (OSHA). (n.d.). Reiteration of existing OSHA policy on indoor air quality: Office temperature/humidity and environmental tobacco smoke. https://www.osha.gov (Accessed February 24, 2025)
104
Occupational Safety and Health Administration. (1992). Technical manual. U.S. Department of Labor.
105
Osman, M. E., Abdel Hameed, A. A., Ibrahim, H. Y., Yousef, F., Abo Elnasr, A. A., & Saeed, Y. (2017). Air microbial contamination and factors affecting its occurrence in certain book libraries in Egypt. Egyptian Journal of Botany, 57 (1), 93–118. https://doi.org/10.21608/ejbo.2016.277.1007
106
Pacharra, M., Kleinbeck, S., Schäper, M., et al. (2016). Multidimensional assessment of self-reported chemical intolerance and its impact on chemosensory effects during ammonia exposure. International Archives of Occupational and Environmental Health, 89 , 947–959. https://doi.org/10.1007/s00420-016-1134-6
107
Park, M., Joo, H. S., Lee, K., Jang, M., Kim, S. D., Kim, I., Borlaza, L. J. S., Lim, H., Shin, H., Chung, K. H., Choi, Y. H., Park, S. G., Bae, M. S., Lee, J., Song, H., & Park, K. (2018). Differential toxicities of fine particulate matters from various sources. Scientific Reports, 8 (1), 17007. https://doi.org/10.1038/s41598-018-35398-0
108
Pepper, I. L., & Gerba, C. P. (2015). Aeromicrobiology. In Environmental microbiology (pp. 89–110). https://doi.org/10.1016/B978-0-12-394626-3.00005-3
109
Pitt, I. J., & Hocking, A. (2009). Fungi and food spoilage. Springer. https://doi.org/10.1007/978-0-387-92207-2
110
Platt, S. D., Martin, C. J., Hunt, S. M., & Lewis, C. W. (1989). Damp housing, mould growth and symptomatic health state. British Medical Journal, 298 , 1673–1678. https://doi.org/10.1136/bmj.298.6689.1673
111
Polish Standards. (1989). PN-89/Z-04111/03 Protection of air cleanness – Enumeration of microscopic fungi in atmospheric air (in Polish).
112
Pyrri, I., Zoma, A., Barmparesos, N., Assimakopoulos, M. N., Assimakopoulos, V. D., & Kapsanaki-Gotsi, E. (2020). Impact of a green roof system on indoor fungal aerosol in a primary school in Greece. Science of The Total Environment, 719 , 137447. https://doi.org/10.1016/j.scitotenv.2020.137447
113
Quintana, Á. R., Seseña, S., Garzón, A., & Arias, R. (2020). Factors affecting levels of airborne bacteria in dairy farms: A review. Animals, 10 (3), 526. https://doi.org/10.3390/ani10030526
114
Quintanilla-Martinez, A., Aguirre-Gutron, L., Espinosa-Chaurand, L., Diaz-Ramirez, M., & Cortes-Sánchez, A. (2022). Microbiological analysis of the air in a popular fish processing and marketing area. Applied Biosciences, 1 (3), 299–314. https://doi.org/10.3390/applbiosci1030019
115
Rai, S., Singh, D. K., & Kumar, A. (2021). Microbial, environmental and anthropogenic factors influencing the indoor microbiome of the built environment. Journal of Basic Microbiology, 61 (4), 265–361. https://doi.org/10.1002/jobm.202000575
116
Raper, K. B., & Fennell, D. I. (1977). The genus Aspergillus. R. E. Krieger Publishing Company.
117
Reponen, T. A., Gazenko, S. V., Grinshpun, S. A., Willeke, K., & Cole, E. C. (1998). Characteristics of airborne actinomycete spores. Applied and Environmental Microbiology, 64 (10), 3807–3812. https://doi.org/10.1128/AEM.64.10.3807-3812.1998
118
Reynolds, S. J., Streifel, A. J., & McJilton, C. E. (1990). Elevated airborne concentrations of fungi in residential and office environments. American Industrial Hygiene Association Journal, 51 (11), 601–604. https://doi.org/10.1080/15298669091370185
119
Rintala, H. (2011). Actinobacteria in indoor environments: Exposures and respiratory health effects. Frontiers in Bioscience-Scholar, 3 (1), 1273–1284. https://doi.org/10.2741/225
120
Rodriguez-Rajo, F. J., Iglesias, I., & Jato, V. (2005). Variation assessment of airborne Alternaria and Cladosporium spores at different bioclimatical conditions. Mycological Research, 109 (Pt. 4), 497–507. https://doi.org/10.1017/S0953756204001777
121
Romano, S. (2023). Bioaerosols: Composition, meteorological impact and transport. Atmosphere, 14 (3), 590. https://doi.org/10.3390/atmos14030590
122
Roshan, S. K., Godini, H., Nikmanesh, B., Bakhshi, H., & Charsizadeh, A. (2019). Study on the relationship between the concentration and type of fungal bioaerosols at indoor and outdoor air in the children’s medical center, Tehran, Iran. Environmental Monitoring and Assessment, 191 (2), 48. https://doi.org/10.1007/s10661-018-7183-4
123
Roumi, S., Zhang, F., Stewart, R. A., & Santamouris, M. (2022). Commercial building indoor environmental quality models: A critical review. Energy and Buildings, 263 (3), 112033. https://doi.org/10.1016/j.enbuild.2022.112033
124
Sabariego, S., Díaz de la Guardia, C., & Alba, F. (2000). The effect of meteorological factors on the daily variation of air-borne fungal spores in Granada (southern Spain). International Journal of Biometeorology, 44 , 1–5. https://doi.org/10.1007/s004840050131
125
Salthammer, T., Mentese, S., & Marutzky, R. (2010). Formaldehyde in the indoor environment. Chemical Reviews, 110 (4), 2536–2572. https://doi.org/10.1021/cr800399g
126
Schäffer, J., Trautman, C., Dill, I., Fischer, G., et al. (2009). Actinomycetes in indoor environments. Gefahrstoffe Reinhaltung der Luft, 69 (9), 335–341.
127
Shiferaw, T., Gebre-Silasse, L., Mulisa, G., Zewidu, A., Belachew, F., Muleta, D., & Zemene, E. (2016). Bacterial indoor-air load and its implications for healthcare-acquired infections in a teaching hospital in Ethiopia. International Journal of Infection Control, 12 (1). https://doi.org/10.3396/ijic.v12i1.15808
128
Sillanpää, M., Saarikoski, S., Hillamo, R., Pennanen, A., Makkonen, U., Spolnik, Z., Van Grieken, R., Koskentalo, T., & Salonen, R. O. (2005). Chemical composition, mass size distribution and source analysis of long-range transported wildfire smokes in Helsinki. Science of The Total Environment, 350 (1–3), 119–135. https://doi.org/10.1016/j.scitotenv.2005.01.024
129
Smets, W., Moretti, S., Denys, S., & Lebeer, S. (2016). Airborne bacteria in the atmosphere: Presence, purpose, and potential. Atmospheric Environment, 139 , 214–221. https://doi.org/10.1016/j.atmosenv.2016.05.038
130
Soleimani, M., Shiran, F., Amir, S., & Jalali, H. (2022). Spatial and temporal variation of bacterial population in ambient air particulate matters (PM2.5, PM10 and TSP) of Isfahan city, Iran. Journal of Air Pollution and Health, 7 (3), 261–274. https://doi.org/10.18502/japh.v7i3.10540
131
Spinazzè, A., Campagnolo, D., Cattaneo, A., Urso, P., Sakellaris, I. A., Saraga, D. E., Mandin, C., et al. (2020). Indoor gaseous air pollutants determinants in office buildings – The OFFICAIR project. Indoor Air, 30 , 76–87. https://doi.org/10.1111/ina.12609
132
Sulaiman, M. A., Wan Yusoff, W. Z., & Wan Kamarudin, W. N. (2013). Evaluation of indoor environmental quality (IEQ) on dense academia Universiti Tun Hussein Onn Malaysia. International Journal of Scientific and Research Publications, 3 (1), 1–5. https://www.ijsrp.org/research-paper-1301.php?rp=P13622
133
Sun, C., Cai, Y., Chen, J., Li, J., Su, C., Zou, Z., & Huang, C. (2024). Indoor ammonia concentrations in college dormitories and the health effects. Journal of Building Engineering, 84 , 108556. https://doi.org/10.1016/j.jobe.2024.108556
134
Sun, C., Hong, S., Cai, G., Zhang, Y., Kan, H., Zhao, Z., Deng, F., Zhao, B., Zeng, X., Sun, Y., Qian, H., Liu, W., Mo, J., Guo, J., Zheng, X., Su, C., Zou, Z., Li, H., & Huang, C. (2021). Indoor exposure levels of ammonia in residences, schools, and offices in China from 1980 to 2019: A systematic review. Indoor Air, 31 (6), 1691–1706. https://doi.org/10.1111/ina.12864
135
Tang, J. W. (2009). The effect of environmental parameters on the survival of airborne infectious agents. Journal of the Royal Society Interface, 6 (6), S737–S746. https://doi.org/10.1098/rsif.2009.0227.focus
136
Tang, H., Ding, Y., & Singer, B. (2020). Interactions and comprehensive effect of indoor environmental quality factors on occupant satisfaction. Building and Environment, 167 , 106462. https://doi.org/10.1016/j.buildenv.2019.106462
137
Tiwari, A., Pandey, M., Tirkey, A., Tiwari, A., Dubey, R., & Pandey, S. K. (2024). Image-based analytical approaches for study of particulate matter (PM) in air. Frontiers in Environmental Science, 12 , 1362422. https://doi.org/10.3389/fenvs.2024.1362422
138
Thorne, P. S. (2019). Industrial livestock production facilities: Airborne emissions. In J. Nriagu (Ed.), Encyclopedia of Environmental Health (2nd ed., pp. 652–660). https://doi.org/10.1016/B978-0-12-409548-9.11862-7
139
Tran, V. V., Park, D., & Lee, Y. C. (2020). Indoor air pollution, related human diseases, and recent trends in the control and improvement of indoor air. International Journal of Environmental Research and Public Health, 17 (8), 2927. https://doi.org/10.3390/ijerph17082927
140
Tuomi, T., & Vainiotalo, S. (2016). The guideline and target values for total volatile organic compound concentrations in industrial indoor environments in Finland. Indoor and Built Environment, 25 (2), 424–434. https://doi.org/10.1177/1420326X14554270
141
Tyagi, S., & Srivastava, A. (2023). Characterization of size-segregated fungal bioaerosols in and around a sugar mill of Western Uttar Pradesh, India. Research Square. https://doi.org/10.21203/rs.3.rs-2407544/v1
142
U.S. Environmental Protection Agency (U.S. EPA). (2025a). Indoor air quality (IAQ). https://www.epa.gov/indoor-air-quality-iaq (Accessed January 2025)
143
U.S. Environmental Protection Agency (U.S. EPA). (2025b). Biological pollutants’ impact on indoor air quality. https://www.epa.gov/indoor-air-quality-iaq/biological-pollutants-impact-indoor-air-quality (Accessed January 2025)
144
Verreault, D., Duchaine, C., Marcoux-Voiselle, M., Turgeon, N., & Roy, C. J. (2014). Design of an environmentally controlled rotating chamber for bioaerosol aging studies. Inhalation Toxicology, 26 (9), 554–558. https://doi.org/10.3109/08958378.2014.928763
145
Wilkie, A. D., Venz, L., & Letters, S. (2023). Outdoor airborne fungal spores in Queensland, Australia. Journal of Bacteriology & Mycology: Open Access, 11 (1), 24–32. https://doi.org/10.15406/jbmoa.2023.11.00339
146
World Health Organization. (2000). Air quality guidelines for Europe (2nd ed.). WHO Regional Publications, European Series No. 91.
147
World Health Organization. (2001). International classification of functioning, disability and health (pp. 1–303). World Health Organization.
148
World Health Organization. (2010). Guidelines for indoor air quality: Selected pollutants. Geneva: WHO.
149
Wolkoff, P. (2008). “Healthy eye” in office-like environments. Environment International, 34 (8), 1204–1214. https://doi.org/10.1016/j.envint.2008.04.005
150
Won, E., & Ross, H. (1969). Reaction of airborne Rhizobium meliloti to some environmental factors. Applied Microbiology, 18 , 555–557. https://doi.org/10.1128/am.18.4.555-557.1969
151
Wu, Q., Li, N., Cai, X., He, Y., & Du, Y. (2023). Impact of indoor environmental quality (IEQ) factors on occupants’ environmental perception and satisfaction in hospital wards. Building and Environment, 245 , 110918. https://doi.org/10.1016/j.buildenv.2023.110918
152
Wyer, E. K., Kelleghan, B. D., Blanes-Vidal, V., Schauberger, G., & Curran, P. T. (2022). Ammonia emissions from agriculture and their contribution to fine particulate matter: A review of implications for human health. Journal of Environmental Management, 323 , 116285. https://doi.org/10.1016/j.jenvman.2022.116285
153
Zhang, H., Sun, W., Li, W., & Wang, Y. (2022). Physical and chemical characterization of fugitive particulate matter emissions of the iron and steel industry. Atmospheric Pollution Research, 13 (1), 101272. https://doi.org/10.1016/j.apr.2021.101272
154
Zhong, X., Qi, J. H., Li, H. T., Dong, L. J., & Gao, D. M. (2016). Seasonal distribution of microbial activity in bioaerosols in the outdoor environment of the Qingdao coastal region. Atmospheric Environment, 140 (Suppl. 1), 506–513. https://doi.org/10.1016/j.atmosenv.2016.06.034
155
Zhu, Y., Guo, S., & Liang, W. (2024). A literature review investigating the impact of temperature and humidity on volatile organic compound emissions from building materials. Building and Environment, 262 , 111845. https://doi.org/10.1016/j.buildenv.2024.111845